Product characteristics |
Number of inputs and outputs |
Number of digital outputs: 2; Number of analogue outputs: 1 |
Measuring range |
0.8…250 l/min |
0.3…82.9 m/s |
0.05…15 m³/h |
|
Process connection |
threaded connection G 1/4 DN8 |
Application |
Application |
for industrial applications |
Media |
compressed air |
Medium temperature [°C] |
-10…60 |
Min. bursting pressure [bar] |
64 |
Min. bursting pressure [MPa] |
6.4 |
Pressure rating [bar] |
16 |
Pressure rating [Mpa] |
1.6 |
Electrical data |
Operating voltage [V] |
18…30 DC; (according to EN 50178 SELV/PELV) |
Current consumption [mA] |
< 80 |
Protection class |
III |
Reverse polarity protection |
yes |
Power-on delay time [s] |
1 |
Inputs / outputs |
Number of inputs and outputs |
Number of digital outputs: 2; Number of analogue outputs: 1 |
Inputs |
Inputs |
counter reset |
Outputs |
Output signal |
switching signal; analogue signal; pulse signal; IO-Link; (configurable) |
Electrical design |
PNP/NPN |
Number of digital outputs |
2 |
Output function |
normally open / normally closed; (parameterisable) |
Max. voltage drop switching output DC [V] |
2.5 |
Permanent current rating of switching output DC [mA] |
150; (per output) |
Number of analogue outputs |
1 |
Analogue current output [mA] |
4…20; (scalable) |
Max. load [Ω] |
500 |
Pulse output |
consumed quantity meter |
Short-circuit protection |
yes |
Type of short-circuit protection |
pulsed |
Overload protection |
yes |
Measuring/setting range |
Measuring range |
0.8…250 l/min |
0.3…82.9 m/s |
0.05…15 m³/h |
|
Display range |
0…300 l/min |
0…99.5 m/s |
0…18 m³/h |
|
Resolution |
0.2 l/min |
0.1 m/s |
0.01 m³/h |
|
Set point SP |
2.2…249.9 l/min |
0.7…82.9 m/s |
0.13…14.99 m³/h |
|
Reset point rP |
0.9…248.7 l/min |
0.3…82.5 m/s |
0.06…14.92 m³/h |
|
Analogue start point ASP |
0…200 l/min |
0…66.3 m/s |
0…12 m³/h |
|
Analogue end point AEP |
50…250 l/min |
16.6…82.9 m/s |
3…15 m³/h |
|
Low flow cut-off LFC |
0.3…2.7 l/min |
0.1…0.9 m/s |
0.02…0.16 m³/h |
|
In steps of |
0.1 l/min |
0.1 m/s |
0.01 m³/h |
|
Pressure monitoring |
Measuring range [bar] |
-1…16 |
Display range [bar] |
-1…20 |
Resolution [bar] |
0.05 |
Set point SP [bar] |
-0.92…16 |
Reset point rP [bar] |
-1…15.92 |
Analogue start point [bar] |
-1…12.8 |
Analogue end point [bar] |
2.2…16 |
In steps of [bar] |
0.01 |
Volumetric flow quantity monitoring |
Measuring range |
0…100000000 m³ |
0…353146667.2 scf |
|
Display range |
0…100000000 m³ |
0…353146667.2 scf |
|
Set point SP |
0.001…10000000 m³ |
0.05…353146667.2 scf |
|
Pulse value |
0.001…10000000 m³ |
0.05…353146667.2 scf |
|
In steps of |
|
Pulse length [s] |
0.01…2 |
Temperature monitoring |
Measuring range |
|
Display range |
|
Resolution |
|
Set point SP |
|
Reset point rP |
|
Analogue start point |
|
Analogue end point |
|
In steps of |
|
Accuracy / deviations |
Temperature coefficient [1/K] |
± 0,07 % MW |
Accuracy (in the me
Sản phẩm cùng loại
Chat qua zalo
Để lại thông tin - Nhận giá ưu đãi
Gọi cho CÔNG NGHIỆP VÀ TỰ ĐỘNG HÓA COZIC để nhận tư vấn tốt nhất
Địa chỉ - CÔNG NGHIỆP VÀ TỰ ĐỘNG HÓA COZIC
78 Hoà Minh 1 - Hoà Minh - Liên Chiểu - Đà Nẵng - Việt Nam
Văn phòng - CÔNG NGHIỆP VÀ TỰ ĐỘNG HÓA COZIC
VP: 16 Vũ Huy Tấn - Hoà Hiệp Nam - Liên Chiểu- Đà Nẵng- Việt Nam
Thông báo sẽ tự động tắt sau 5 giây ...
|