Product characteristics |
Number of inputs and outputs |
Number of digital outputs: 2 |
Factory setting |
hydrous coolants; water; media similar to water |
Probe length L [mm] |
472 |
Application |
Special feature |
Gold-plated contacts |
Media |
hydrous coolants; oils; oil-based media; water; media similar to water |
Dielectric constant of the medium |
> 2 |
Cannot be used for |
extremely conductive media; adhering media; granulates; bulk material; acids; alkali; hygienic areas and electroplating applications |
Tank pressure [bar] |
0.5; (unpressurized for applications to WHG (German Federal Water Act)) |
Coolants |
Medium temperature [°C] |
0…35; (with climatic tube E43101: 35…60 °C; not for applications to WHG (German Federal Water Act)) |
Oil |
Medium temperature [°C] |
0…70 |
Medium temperature short time [°C] |
0…90; (< 1 h) |
Maximum speed of the change of level [mm/s] |
200 |
Water |
Medium temperature [°C] |
0…35; (with climatic tube E43101: 35…60 °C; not for applications to WHG (German Federal Water Act)) |
Electrical data |
Operating voltage [V] |
12…30 DC |
Current consumption [mA] |
< 50 |
Protection class |
III |
Reverse polarity protection |
yes |
Power-on delay time [s] |
< 3 |
Inputs / outputs |
Number of inputs and outputs |
Number of digital outputs: 2 |
Outputs |
Total number of outputs |
2 |
Output signal |
switching signal; IO-Link |
Electrical design |
PNP/NPN |
Number of digital outputs |
2 |
Max. voltage drop switching output DC [V] |
2.5 |
Permanent current rating of switching output DC [mA] |
200 |
Short-circuit protection |
yes |
Type of short-circuit protection |
pulsed |
Overload protection |
yes |
Measuring/setting range |
Factory setting |
hydrous coolants; water; media similar to water |
Probe length L [mm] |
472 |
Active range A [mm] |
390 |
Inactive range I1 / I2 [mm] |
60 / 22 |
Setting range |
Set point SP [mm] |
35…390 |
Reset point rP [mm] |
30…385 |
In steps of [mm] |
5 |
Reference point OP [mm] |
139 – 163 – 188 – 212 – 236 – 261 – 285 – 310 – 334 – 358 – 383 – 407 – OFF |
Hysteresis, OP [mm] |
3 |
Accuracy / deviations |
Measuring error [% of the final value] |
± 5 |
Repeatability |
± 2 |
Resolution [mm] |
5 |
Software / programming |
Parameter setting options |
hysteresis / window; normally open / normally closed; switching logic; SP/rP position; adjustment OP; medium selection; offset setting; switch-on/switch-off delay |
Interfaces |
Communication interface |
IO-Link |
Transmission type |
COM2 (38,4 kBaud) |
IO-Link revision |
1.1 |
SDCI standard |
IEC 61131-9 |
Profiles |
Smart Sensor: Process Data Variable; Device Identification, Device Diagnosis |
SIO mode |
yes |
Required master port type |
A |
Process data analogue |
3 |
Process data binary |
2 |
Min. process cycle time [ms] |
3.2 |
Supported DeviceIDs |
Type of operation |
DeviceID |
Default |
803 |
|
Operating conditions |
Ambient temperature [°C] |
0…60 |
Storage temperature [°C] |
-25…80 |
Protection |
IP 67 |
Mechanical data |
Weight [g] |
450.9 |
Dimensions [mm] |
Ø 16 |
Materials |
stainless steel (1.4301 / 304); stainless steel (1.4404 / 316L); FKM; NBR; PBT; PC; PA; PP; TPV |
Materials (wetted parts) |
PP |
Displays / operating elements |
Display |
Display unit |
2 x LED, green (cm, inch) |
switching status |
2 x LED, yellow |
measured values |
alphanumeric display, 4-digit |
parameter setting |
alphanumeric display, 4-digit |
|
Remarks |
Pack quantity |
1 pcs. |
Electrical connection |
Connection |
Connector: 1 x M12; Contacts: gold-plated |