| Product characteristics |
| Number of inputs and outputs |
Number of digital outputs: 1; Number of analogue outputs: 1 |
| Probe length L [mm] |
100…1600 |
| Process connection |
G 3/4 external thread |
| Application |
| Special feature |
Gold-plated contacts |
| Media |
Liquids |
| Dielectric constant of the medium |
≥ 1,8; (for media with a dielectric constant of 1.8…5 (e.g. oils), a coaxial pipe is needed for operation) |
| Recommended media |
water; hydrous media; oils; oil-based media |
| Cannot be used for |
See the operating instructions, chapter “Function and features”. |
| Medium temperature [°C] |
-25…80; (90 < 1 h) |
| Tank pressure [bar] |
-1…16 |
| MAWP (for applications according to CRN) [bar] |
16 |
| Electrical data |
| Operating voltage [V] |
18…30 DC |
| Current consumption [mA] |
< 25 |
| Protection class |
III |
| Reverse polarity protection |
yes |
| Power-on delay time [s] |
< 3 |
| Inputs / outputs |
| Number of inputs and outputs |
Number of digital outputs: 1; Number of analogue outputs: 1 |
| Outputs |
| Total number of outputs |
2 |
| Output signal |
analogue signal; IO-Link |
| Electrical design |
PNP |
| Number of digital outputs |
1 |
| Number of analogue outputs |
1 |
| Analogue current output [mA] |
4…20, invertible |
| Max. load [Ω] |
500 |
| Analogue voltage output [V] |
0…10, invertible |
| Min. load resistance [Ω] |
2000 |
| Short-circuit protection |
yes |
| Type of short-circuit protection |
thermal, pulsed |
| Overload protection |
yes |
| Measuring/setting range |
| Probe length L [mm] |
100…1600 |
| Active range A [mm] |
L-40; (when set to oil and oil based media: L-60) |
| Inactive range I1 / I2 [mm] |
30 / 10; (when set to oil and oil based media: 30 / 30) |
| Sampling rate [Hz] |
4 |
| Accuracy / deviations |
| Repeatability [mm] |
± 5 |
| Measuring error [mm] |
± 7 |
| Offset error [mm] |
5 |
| Resolution [mm] |
1 |
| Zero signal (voltage) [V] |
0 |
| Zero signal (current) [mA] |
4 |
| Full signal (voltage) [V] |
10 |
| Full signal (current) [mA] |
20 |
| Temperature drift per 10 K |
± 0.2 % |
| Interfaces |
| Communication interface |
IO-Link |
| Transmission type |
COM2 (38,4 kBaud) |
| IO-Link revision |
1.1 |
| SDCI standard |
IEC 61131-9 CDV |
| Profiles |
no profile |
| SIO mode |
no |
| Required master port type |
A |
| Process data analogue |
1 |
| Min. process cycle time [ms] |
2.3 |
| Supported DeviceIDs |
| Type of operation |
DeviceID |
| Default |
578 |
|
| Operating conditions |
| Ambient temperature [°C] |
-25…60 |
| Storage temperature [°C] |
-40…85 |
| Protection |
IP 68; IP 69K; (7 days / 1 m water depth / 0.1 bar: IP 68) |
| Mechanical data |
| Weight [g] |
430 |
| Materials |
stainless steel (1.4301 / 304); stainless steel (1.4404 / 316L); FKM; PEI |
| Materials (wetted parts) |
stainless steel (1.4305 / 303); probe connection: stainless steel (1.4435 / 316L); PTFE; FKM; Sealing: NBR reinforced fibre |
| Process connection |
G 3/4 external thread |
| Remarks |
| Notes |
Please see the technical note under “Downloads” |
| Pack quantity |
1 pcs. |
| Electrical connection |
| Connection |
Connector: 1 x M12; Contacts: gold-plated |