Product characteristics |
Number of inputs and outputs |
Number of digital outputs: 4 |
Factory setting |
2 switching outputs level (OUT1, OUT2); 2 switching outputs temperature (OUT3, OUT4); mineral oils |
Probe length L [mm] |
264 |
Application |
Media |
hydrous coolants; oils; oil-based media; water; media similar to water |
Dielectric constant of the medium |
> 2 |
Cannot be used for |
extremely conductive media; adhering media; granulates; bulk material; acids; alkali |
Tank pressure [bar] |
0.5; (when mounting with mounting accessories: E43001 – E43007, E43019) |
Coolants |
Medium temperature [°C] |
0…35; (with climatic tube E43100 35…65 °C) |
Oil |
Medium temperature [°C] |
0…70 |
Medium temperature short time [°C] |
0…90; (< 1 h) |
Water |
Medium temperature [°C] |
0…35; (with climatic tube E43100 35…65 °C) |
Electrical data |
Operating voltage [V] |
18…30 DC |
Current consumption [mA] |
< 50 |
Protection class |
III |
Reverse polarity protection |
yes |
Power-on delay time [s] |
< 3 |
Inputs / outputs |
Number of inputs and outputs |
Number of digital outputs: 4 |
Outputs |
Total number of outputs |
4 |
Output signal |
switching signal; IO-Link |
Electrical design |
PNP/NPN |
Number of digital outputs |
4 |
Output function |
normally open / normally closed; (parameterisable) |
Max. voltage drop switching output DC [V] |
2.5 |
Permanent current rating of switching output DC [mA] |
200 |
Short-circuit protection |
yes |
Type of short-circuit protection |
thermal, pulsed |
Overload protection |
yes |
Measuring/setting range |
Factory setting |
2 switching outputs level (OUT1, OUT2); 2 switching outputs temperature (OUT3, OUT4); mineral oils |
Probe length L [mm] |
264 |
Active range A [mm] |
195 |
Inactive range I1 / I2 [mm] |
53 / 16 |
Setting range |
Set point SP [mm] |
25…190 |
Reset point rP [mm] |
20…195 |
In steps of [mm] |
5 |
Reference point OP [mm] |
69 – 82 – 94 – 106 – 118 – 130 – 143 – 155 – 167 – 179 – 191 – 204 – OFF |
Hysteresis, OP [mm] |
2 |
Temperature monitoring |
Measuring range [°C] |
0…90 |
Set point SP [°C] |
0.5…90 |
Reset point rP [°C] |
0…89.5 |
In steps of [°C] |
0.5 |
Resolution of switching output [K] |
0.5 |
Accuracy / deviations |
Measuring error [% of the final value] |
± 5 |
Repeatability |
± 2 |
Resolution [mm] |
5 |
Temperature monitoring |
Switch point accuracy [K] |
± 1,5 |
Resolution [K] |
0.5 |
Dynamic response T09 [s] |
90 |
Software / programming |
Parameter setting options |
hysteresis / window; normally open / normally closed; SP/rP position; OP position; adjustment OP; medium selection; offset setting; Display unit; process value assignment |
Interfaces |
Communication interface |
IO-Link |
Transmission type |
COM2 (38,4 kBaud) |
IO-Link revision |
1.1 |
SDCI standard |
IEC 61131-9 |
Profiles |
Smart Sensor: Process Data Variable; Device Identification, Device Diagnosis |
SIO mode |
yes |
Required master port type |
A |
Process data analogue |
4 |
Process data binary |
4 |
Min. process cycle time [ms] |
4.5 |
Supported DeviceIDs |
Type of operation |
DeviceID |
Default |
18 |
|
Operating conditions |
Ambient temperature [°C] |
0…60 |
Storage temperature [°C] |
-25…80 |
Protection |
IP 67 |
Mechanical data |
Weight [g] |
362.5 |
Dimensions [mm] |
Ø 16 |
Materials |
stainless steel (1.4301 / 304); stainless steel (1.4404 / 316L); FKM; NBR; PBT; PC; PP; PA; TPV |
Materials (wetted parts) |
PP |
Displays / operating elements |
Display |
Display unit |
4 x LED, green (cm, inch, °C, °F) |
switching status |
4 x LED, yellow (OUT4…OUT1) |
measured values |
alphanumeric display, 4-digit |
parameter setting |
alphanumeric display, 4-digit |
|
Remarks |
Notes |
For 8-pole sockets the core colours are not standardised.; Please note the wiring of the sensor and the sockets (see data sheet).; Please see the technical note under “Downloads” |
Pack quantity |
1 pcs. |
Electrical connection |
Connection |
Connector: 1 x M12 |