Number of digital outputs: 2; Number of analogue outputs: 1
Process connection
threaded connection 1″ NPT
Temperature monitoring
Measuring range [°F]
14…212
Application
Special feature
Gold-plated contacts
Application
for industrial applications
Media
water; glycol solutions; coolants; oil
Note on media
oil 1 with viscosity: 10 mm²/s (40 °C)
oil 2 with viscosity: 46 mm²/s (40 °C)
Medium temperature [°F]
14…212
Pressure rating [bar]
25
Pressure rating [Mpa]
2.5
MAWP (for applications according to CRN) [bar]
25
Electrical data
Operating voltage [V]
18…30 DC; (according to EN 50178 SELV/PELV)
Current consumption [mA]
< 50
Protection class
III
Reverse polarity protection
yes
Power-on delay time [s]
< 3
Inputs / outputs
Number of inputs and outputs
Number of digital outputs: 2; Number of analogue outputs: 1
Outputs
Total number of outputs
2
Output signal
switching signal; analogue signal; frequency signal; IO-Link; (configurable)
Number of digital outputs
2
Output function
normally open / normally closed; (parameterisable)
Max. voltage drop switching output DC [V]
2
Permanent current rating of switching output DC [mA]
150; (per output 2 x 200 (…60 °C); 2 x 250 (…40 °C))
Switching cycles (mechanical)
10 million
Number of analogue outputs
1
Analogue current output [mA]
4…20
Max. load [Ω]
500
Short-circuit protection
yes
Overload protection
yes
Frequency of the output [Hz]
0…10000
Measuring/setting range
Measuring range [gph]
30…1620
Display range
0…1940 gph
0…32.4 gpm
Resolution
10 gph
0.1 gpm
Set point SP
10…1620 gph
0.2…27 gpm
Reset point rP
0…1610 gph
0…26.8 gpm
Frequency end point, FEP
110…1620 gph
1.8…27 gpm
In steps of
10 gph
0.1 gpm
Frequency at the end point FRP [Hz]
10…10000
Measuring dynamics
1:50
Temperature monitoring
Measuring range [°F]
14…212
Display range [°F]
-26…252
Resolution [°F]
2
Set point SP [°F]
16…212
Reset point rP [°F]
14…210
In steps of [°F]
2
Frequency start point, FSP [°F]
14…172
Frequency end point, FEP [°F]
54…212
Frequency at the end point FRP [Hz]
10…10000
Accuracy / deviations
Flow monitoring
Accuracy (in the measuring range)
± (4 % MW + 1 % MEW); (Q > 2 l/min; medium and operating temperature: +22 °C ± 4K)
Repeatability
± 1 % MEW
Temperature monitoring
Temperature drift
0,029 °C / K
Accuracy [K]
3 K (25°C; Q > 1 l/min)
Response times
Flow monitoring
Response time [s]
0.01
Damping for the switching output dAP [s]
0…5
Damping for the analogue output dAA [s]
0…5
Temperature monitoring
Dynamic response T05 / T09 [s]
T09 = 120 (Q > 1 l/min)
Software / programming
Parameter setting options
hysteresis / window; normally open / normally closed; switching logic; current output; medium selection; damping for the switching output / analogue output; display can be rotated and switched off; standard unit of measurement; process value colour
Interfaces
Communication interface
IO-Link
Transmission type
COM2 (38,4 kBaud)
IO-Link revision
1.1
SDCI standard
IEC 61131-9 CDV
Profiles
Smart Sensor: Process Data Variable; Device Identification