Bộ khuếch đại cảm biến mức Keyence FL-C001

Model FL-C001
Type Plastic type
Measurement range 200 to 2,000 mm 7.87″ to 78.74″
Specific conductive capacity of measurable media 3 or more*1
Resolution 1 mm 0.04″*2
Linearity ±3 mm ±0.12″*2
Temperature characteristics 0.1 mm/°C
Undetectable area In the case of water Top side 25 mm 0.98″
Bottom side 33 mm 1.30″ max.*3
In the case of oil Top side 25 mm 0.98″
Bottom side 53 mm 2.09″ max.*3
Judgment output response time 0.4 s minimum
Probe horizontal torque 6 N m
Tank pressure -0.1 to +0.1 Mpa
Connection port G3/4 on the dedicated probe side
Control output Judgment output/alarm output NPN/PNP open collector (selectable), 30 VDC max., 50 mA max. for eachResidual voltage: 2 V max. for NPN, 2.5 V max. for PNP, N.O./N.C. switchable
Analog output 4 to 20 mA, maximum load resistance: 350 Ω (Response time: 0.1 s after comparator output determined [90 % response])Ripple when target remains stationary (P-P) 2 % of F.S. max.
Network compatibility IO-Link*4
Analog output accuracy Resolution 1 mm 0.04″
Zero accuracy ±0.1 mA (Zero point = 4 mA)
Full scale accuracy ±0.2 mA (full scale = 20 mA)
Applicable cable 8-pin M12 connector
Rating Power voltage 10 to 30 VDC, ripple (P-P) 10% included, Class 2 or LPS
Current consumption 300 mA max. (at 10 V)/120 mA max. (at 30 V) (excluding load)
Environmental resistance Enclosure rating IP67
Ambient temperature -10 to +60 °C 14 to 140 °F
Relative humidity 35 to 85 % RH (No condensation)
Operating medium temperature -10 to +110 °C 14 to 230 °F
Vibration resistance 10 to 55 Hz, 0.75 mm 0.03″ double amplitude in X, Y and Z directions, 2 hours respectively
Shock resistance 300 m/s2 in 6 directions, 3 times respectively
Material Liquid end materials Sheath: PFAProbe: SUS304(do not connect this directly)
Case Plastic section of the housing: PPS, PPSU, FKM, PVCCable connector: Ni-plated brass
Weight 380 g