| Product characteristics |
| Output signal |
switching signal; analogue signal; IO-Link; (configurable) |
| Measuring range |
| -1…100 bar |
-15…1450 psi |
-0.1…10 MPa |
|
| Process connection |
threaded connection G 1 external thread sealing cone |
| Application |
| Special feature |
Gold-plated contacts |
| Application |
food and beverage industry |
| Media |
viscous media and liquids with suspended particles; liquids and gases |
| Conditionally suitable for |
use in gases at pressures > 25 bar only on request |
| Medium temperature [°C] |
-25…125; (145 max. 1h) |
| Min. bursting pressure |
|
| Pressure rating |
|
| Vacuum resistance [mbar] |
-1000 |
| Type of pressure |
relative pressure; vacuum |
| No dead space |
yes |
| Electrical data |
| Min. insulation resistance [MΩ] |
100; (500 V DC) |
| Protection class |
III |
| Reverse polarity protection |
yes |
| Integrated watchdog |
yes |
| 2-wire |
| Operating voltage [V] |
20…32 DC |
| Current consumption [mA] |
3.6…21 |
| Power-on delay time [s] |
1 |
| 3-wire |
| Operating voltage [V] |
18…32 DC |
| Current consumption [mA] |
< 45 |
| Power-on delay time [s] |
0.5 |
| Inputs / outputs |
| Number of inputs and outputs |
Number of digital outputs: 2; Number of analogue outputs: 1 |
| Outputs |
| Total number of outputs |
2 |
| Output signal |
switching signal; analogue signal; IO-Link; (configurable) |
| Electrical design |
PNP/NPN |
| Number of digital outputs |
2 |
| Output function |
normally open / normally closed; (parameterisable) |
| Number of analogue outputs |
1 |
| Analogue current output [mA] |
4…20, invertible; (scalable) |
| Short-circuit protection |
yes |
| Type of short-circuit protection |
pulsed |
| Overload protection |
yes |
| 2-wire |
| Max. load [Ω] |
300 |
| 3-wire |
| Max. voltage drop switching output DC [V] |
2 |
| Permanent current rating of switching output DC [mA] |
250 |
| Switching frequency DC [Hz] |
125 |
| Max. load [Ω] |
(Ub – 10 V) / 20 mA |
| Measuring/setting range |
| Measuring range |
| -1…100 bar |
-15…1450 psi |
-0.1…10 MPa |
|
| Set point SP |
| -0.8…100 bar |
-12…1450 psi |
-0.08…10 MPa |
|
| Reset point rP |
| -1…99.8 bar |
-15…1448 psi |
-0.1…9.98 MPa |
|
| Analogue start point |
| -1…75 bar |
-15…1088 psi |
-0.1…7.5 MPa |
|
| Analogue end point |
| 24…100 bar |
348…1450 psi |
2.4…10 MPa |
|
| In steps of |
|
| Factory setting |
| |
SP1 = 25.0 bar |
rP1 = 23 bar |
| |
SP2 = 75.0 bar |
rP2 = 73 bar |
| |
ASP = 0.0 bar |
AEP = 100.0 bar |
|
| Accuracy / deviations |
| Switch point accuracy [% of the span] |
< ± 0,5; (Turn down 1:1) |
| Repeatability [% of the span] |
< ± 0,1; (with temperature fluctuations < 10 K; Turn down 1:1) |
| Characteristics deviation [% of the span] |
< ± 0,5; (Turn down 1:1 linearity, incl. hysteresis and repeatability limit value setting to DIN 16086) |
| Linearity deviation [% of the span] |
< ± 0,15; (Turn down 1:1) |
| Hysteresis deviation [% of the span] |
< ± 0,15; (Turn down 1:1) |
| Long-term stability [% of the span] |
< ± 0,1; (Turn down 1:1; per year) |
| Temperature coefficient zero point [% of the span / 10 K] |
< ± 0,2; (0…70 °C) |
| Temperature coefficient span [% of the span / 10 K] |
< ± 0,2; (0…70 °C) |
| Response times |
| Damping for the switching output dAP [s] |
0…30 |
| Damping for the analogue output dAA [s] |
0.01…99.99 |
| 2-wire |
| Step response time analogue output [ms] |
45 |
| 3-wire |
| Min. response time of switching output (dAP) [ms] |
3 |
| Step response time analogue output [ms] |
7 |
| Interfaces |
| Communication interface |
IO-Link |
| Transmission type |
COM2 (38,4 kBaud) |
| IO-Link revision |
1.0 |
| Profiles |
no profile |
| SIO mode |
yes |
| Required master port type |
A |
| Process data analogue |
1 |
| Process data binary |
2 |
| Min. process cycle time [ms] |
2.3 |
| Supported DeviceIDs |
| Type of operation |
DeviceID |
| Default |
731 |
|
| Operating conditions |
| Ambient temperature [°C] |
-25…80 |
| Storage temperature [°C] |
-40…100 |
| Protection |
IP 67; IP 68; IP 69K |
| Mechanical data |
| Weight [g] |
374 |
| Materials |
stainless steel (1.4404 / 316L); FKM; PTFE; PBT; PEI; PFA |
| Materials (wetted parts) |
ceramics (99.9 % Al2O3); stainless steel (1.4435 / 316L); surface characteristics: Ra < 0,4 / Rz 4; PTFE |
| Min. pressure cycles |
100 million |
| Process connection |
threaded connection G 1 external thread sealing cone |
| Displays / opera
Sản phẩm cùng loại
Chat qua zalo
Để lại thông tin - Nhận giá ưu đãi
Gọi cho CÔNG NGHIỆP VÀ TỰ ĐỘNG HÓA COZIC để nhận tư vấn tốt nhất
Địa chỉ - CÔNG NGHIỆP VÀ TỰ ĐỘNG HÓA COZIC
78 Hoà Minh 1 - Hoà Minh - Liên Chiểu - Đà Nẵng - Việt Nam
Văn phòng - CÔNG NGHIỆP VÀ TỰ ĐỘNG HÓA COZIC
VP: 16 Vũ Huy Tấn - Hoà Hiệp Nam - Liên Chiểu- Đà Nẵng- Việt Nam
Thông báo sẽ tự động tắt sau 5 giây ...
|