Cảm biến áp suất IFM PN2098 -0.0125…0.25 bar

Product characteristics
Output signal switching signal; analogue signal; IO-Link; (configurable)
Measuring range
 
-0.0125…0.25 bar -12.5…250 mbar -5…100.4 inH2O -1.25…25 kPa -127…2549 mmWS
Process connection threaded connection G 1/4 internal thread (DIN EN ISO 1179-2)
Application
Special feature Gold-plated contacts
Measuring element ceramic-capacitive pressure measuring cell
Application for industrial applications
Media liquids and gases
Medium temperature [°C] -25…80
Min. bursting pressure
 
30000 mbar 12000 inH2O 3000 kPa 306000 mmWS
Pressure rating
 
10000 mbar 4000 inH2O 1000 kPa 102000 mmWS
Vacuum resistance [mbar] -1000
Type of pressure relative pressure
Electrical data
Operating voltage [V] 18…30 DC; (according to EN 50178 SELV/PELV)
Current consumption [mA] < 35
Min. insulation resistance [MΩ] 100; (500 V DC)
Protection class III
Reverse polarity protection yes
Power-on delay time [s] 0.3
Integrated watchdog yes
Inputs / outputs
Number of inputs and outputs Number of digital outputs: 2; Number of analogue outputs: 1
Outputs
Total number of outputs 2
Output signal switching signal; analogue signal; IO-Link; (configurable)
Electrical design PNP/NPN
Number of digital outputs 2
Output function normally open / normally closed; (parameterisable)
Max. voltage drop switching output DC [V] 2
Permanent current rating of switching output DC [mA] 250
Switching frequency DC [Hz] < 500
Number of analogue outputs 1
Analogue current output [mA] 4…20; (scalable 1:5)
Max. load [Ω] 500
Analogue voltage output [V] 0…10; (scalable 1:5)
Min. load resistance [Ω] 2000
Short-circuit protection yes
Type of short-circuit protection pulsed
Overload protection yes
Measuring/setting range
Measuring range
 
-0.0125…0.25 bar -12.5…250 mbar -5…100.4 inH2O -1.25…25 kPa -127…2549 mmWS
Analogue start point
 
-12.5…200 mbar -5…80.2 inH2O -1.25…20 kPa -125…2040 mmWS
Analogue end point
 
37.5…250 mbar 15…100.4 inH2O 3.75…25 kPa 385…2550 mmWS
Factory setting / CMPT = 2
Set point SP
 
-10.9…250 mbar -4.4…100.4 inH2O -1.09…25 kPa -112…2550 mmWS
Reset point rP
 
-12…249 mbar -4.8…100 inH2O -1.2…24.9 kPa -122…2539 mmWS
Min. difference between SP and rP
 
1.5 mbar 0.6 inH2O 0.15 kPa 15 mmWS
In steps of
 
0.1 mbar 0.1 inH2O 0.01 kPa 1 mmWS
Status_B High Resolution / CMPT = 3
Set point SP
 
-11…250 mbar -4.4…100.4 inH2O -1.1…25 kPa -110…2550 mmWS
Reset point rP
 
-12…249 mbar -4.8…100 inH2O -1.2…24.9 kPa -120…2540 mmWS
Min. difference between SP and rP
 
1.1 mbar 0.5 inH2O 0.11 kPa 11 mmWS
In steps of
 
0.5 mbar 0.2 inH2O 0.05 kPa 5 mmWS
Accuracy / deviations
Notes on the accuracy / deviation switch point accuracy, linearity error under DNV GL: < ± 1%: < ± 1%
Switch point accuracy [% of the span] < ± 0,4; (Turn down 1:1)
Repeatability [% of the span] < ± 0,1; (with temperature fluctuations < 10 K; Turn down 1:1)
Characteristics deviation [% of the span] < ± 0,25 (BFSL) / < ± 0,5 (LS); (Turn down 1:1; BFSL = Best Fit Straight Line; LS = limit value setting)
Hysteresis deviation [% of the span] < ± 0,1; (Turn down 1:1)
Long-term stability [% of the span] < ± 0,05; (Turn down 1:1; per 6 months)
Temperature coefficient zero point [% of the span / 10 K] < ± 0,2; (-0…80 °C)
Temperature coefficient span [% of the span / 10 K] < ± 0,2; (-0…80 °C)
Response times
Response time [ms] < 1.5
Delay time programmable dS, dr [s] 0…50
Damping for the switching output dAP [s] 0…4
Damping for the analogue output dAA [s] 0…4
Max. response time analogue output [ms] 3
Software / programming
Parameter setting options hysteresis / window; normally open / normally closed; switch-on/switch-off delay; Damping; Display unit; current/voltage output
Interfaces
Communication interface IO-Link
Transmission type COM2 (38,4 kBaud)
IO-Link revision 1.1
SDCI standard IEC 61131-9
SIO mode yes
Required master port type A; (wenn PIN 2 nicht verbunden: B)