| Product characteristics |
| Output signal |
switching signal |
| Measuring range |
| 0…25 bar |
0…363 psi |
0…2.5 MPa |
|
| Process connection |
threaded connection 1/4″ NPT internal thread |
| Application |
| Application |
for industrial applications |
| Media |
liquids and gases |
| Medium temperature [°C] |
-25…80 |
| Min. bursting pressure |
|
| Pressure rating |
|
| Type of pressure |
relative pressure |
| Electrical data |
| Operating voltage tolerance [%] |
5…10 |
| Operating voltage [V] |
85…265 AC |
| Nominal voltage AC [V] |
< 250 |
| Current consumption [mA] |
< 10 |
| Min. insulation resistance [MΩ] |
100; (500 V DC) |
| Protection class |
II |
| Reverse polarity protection |
no |
| Power-on delay time [s] |
0.2 |
| Integrated watchdog |
yes |
| Inputs / outputs |
| Number of inputs and outputs |
Number of digital outputs: 1 |
| Outputs |
| Total number of outputs |
1 |
| Output signal |
switching signal |
| Electrical design |
Triac |
| Number of digital outputs |
1 |
| Output function |
normally open / normally closed; (parameterisable) |
| Max. voltage drop switching output AC [V] |
2 |
| Permanent current rating of switching output AC [mA] |
250; ((…70 °C) 1000 (…60 °C) 1500 (…45 °C) 2500 (…20 °C)) |
| Switching frequency AC [Hz] |
< 160 |
| Short-circuit proof |
no |
| Overload protection |
no |
| Measuring/setting range |
| Measuring range |
| 0…25 bar |
0…363 psi |
0…2.5 MPa |
|
| Set point SP |
| 0.2…25 bar |
4…363 psi |
0.02…2.5 MPa |
|
| Reset point rP |
| 0.1…24.9 bar |
2…362 psi |
0.01…2.49 MPa |
|
| In steps of |
|
| Accuracy / deviations |
| Switch point accuracy [% of the span] |
< ± 1,0 |
| Repeatability [% of the span] |
< ± 0,1; (with temperature fluctuations < 10 K) |
| Linearity deviation [% of the span] |
< ± 0,5 |
| Hysteresis deviation [% of the span] |
< ± 0,1 |
| Long-term stability [% of the span] |
< ± 0,1; (per year) |
| Temperature coefficient zero point [% of the span / 10 K] |
< ± 0,2; (-25…80 °C) |
| Temperature coefficient span [% of the span / 10 K] |
< ± 0,3; (-25…80 °C) |
| Response times |
| Delay time programmable dS, dr [s] |
0, 0,2,…10, 11,…50 |
| Damping for the switching output dAP [s] |
0…4 |
| Software / programming |
| Adjustment of the switch point |
programming button |
| Parameter setting options |
hysteresis / window; normally open / normally closed; switch-on/switch-off delay; Damping; adaptation of displayed values; display can be rotated and switched off; Display unit |
| Operating conditions |
| Ambient temperature [°C] |
-25…80 |
| Storage temperature [°C] |
-40…100 |
| Protection |
IP 65 |
| Mechanical data |
| Weight [g] |
390 |
| Materials |
stainless steel (1.4301 / 304); PC; PBT; PA; FKM |
| Materials (wetted parts) |
stainless steel (1.4305 / 303); ceramics; FKM |
| Min. pressure cycles |
100 million |
| Process connection |
threaded connection 1/4″ NPT internal thread |
| Restrictor element integrated |
no (can be retrofitted) |
| Displays / operating elements |
| Display |
| switching status |
LED, red |
| function display |
7-segment LED display |
| measured values |
7-segment LED display |
|
| Electrical connection |
| Required protection |
miniature fuse to IEC60127-2 sheet 1; ≤ 5 A; fast acting |
| Remarks |
| Remarks |
|
| Pack quantity |
1 pcs. |
| Electrical connection |
| Connection |
Connector: 1 x 1/2″ |