| Product characteristics |
| Output signal |
switching signal; IO-Link; (configurable) |
| Measuring range |
| 0…100 bar |
0…1450 psi |
0…10 MPa |
|
| Process connection |
threaded connection G 1/4 internal thread |
| Application |
| Special feature |
Gold-plated contacts |
| Measuring element |
ceramic-capacitive pressure measuring cell |
| Application |
for industrial applications |
| Media |
Liquids |
| Conditionally suitable for |
use in gases at pressures > 25 bar only on request |
| Medium temperature [°C] |
-25…80 |
| Min. bursting pressure |
|
| Pressure rating |
|
| Vacuum resistance [mbar] |
-1000 |
| Type of pressure |
relative pressure |
| Electrical data |
| Operating voltage [V] |
18…30 DC; (according to EN 50178 SELV/PELV) |
| Current consumption [mA] |
< 35 |
| Min. insulation resistance [MΩ] |
100; (500 V DC) |
| Protection class |
III |
| Reverse polarity protection |
yes |
| Power-on delay time [s] |
< 0.3 |
| Integrated watchdog |
yes |
| Inputs / outputs |
| Number of inputs and outputs |
Number of digital outputs: 2 |
| Outputs |
| Total number of outputs |
2 |
| Output signal |
switching signal; IO-Link; (configurable) |
| Electrical design |
PNP/NPN |
| Number of digital outputs |
2 |
| Output function |
normally open / normally closed; (parameterisable) |
| Max. voltage drop switching output DC [V] |
2.5 |
| Permanent current rating of switching output DC [mA] |
150; (200 (…60 °C) 250 (…40 °C)) |
| Switching frequency DC [Hz] |
< 170 |
| Short-circuit protection |
yes |
| Type of short-circuit protection |
pulsed |
| Overload protection |
yes |
| Measuring/setting range |
| Measuring range |
| 0…100 bar |
0…1450 psi |
0…10 MPa |
|
| Factory setting / CMPT = 2 |
| Set point SP |
| 1…100 bar |
10…1450 psi |
0.1…10 MPa |
|
| Reset point rP |
| 0.5…99.5 bar |
5…1445 psi |
0.05…9.95 MPa |
|
| Min. difference between SP and rP |
|
| In steps of |
|
| Status_B High Resolution / CMPT = 3 |
| Set point SP |
| 0.8…100 bar |
12…1450 psi |
0.08…10 MPa |
|
| Reset point rP |
| 0.3…99.5 bar |
5…1443 psi |
0.03…9.95 MPa |
|
| Min. difference between SP and rP |
|
| In steps of |
|
| Accuracy / deviations |
| Switch point accuracy [% of the span] |
< ± 0,5 |
| Repeatability [% of the span] |
< ± 0,1; (with temperature fluctuations < 10 K) |
| Characteristics deviation [% of the span] |
< ± 0,25 (BFSL) / < ± 0,5 (LS); (BFSL = Best Fit Straight Line; LS = limit value setting) |
| Hysteresis deviation [% of the span] |
< ± 0,25 |
| Long-term stability [% of the span] |
< ± 0,05; (per 6 months) |
| Temperature coefficient zero point [% of the span / 10 K] |
< ± 0,2; (-0…80 °C) |
| Temperature coefficient span [% of the span / 10 K] |
< ± 0,2; (-0…80 °C) |
| Response times |
| Response time [ms] |
< 3 |
| Delay time programmable dS, dr [s] |
0…50 |
| Software / programming |
| Parameter setting options |
hysteresis / window; normally open / normally closed; switching logic; switch-on/switch-off delay; Damping; Display unit |
| Interfaces |
| Communication interface |
IO-Link |
| Transmission type |
COM2 (38,4 kBaud) |
| IO-Link revision |
1.1 |
| SDCI standard |
IEC 61131-9 |
| SIO mode |
yes |
| Required master port type |
A; (when pin 2 not connected: B) |
| Process data analogue |
1 |
| Process data binary |
2 |
| Supported DeviceIDs |
| Type of operation |
DeviceID |
| Factory setting / CMPT = 2 |
401 |
| Status_B High Resolution / CMPT = 3 |
599 |
| PN7002 |
309 |
|
| Note |
| For further information please see the IODD PDF file under “Downloads” |
|
| Factory setting / CMPT = 2 |
| Profiles |
Smart Sensor: Process Data Variable; Device Identification, Device Diagnosis |
| Min. process cycle time [ms] |
2.3 |
| IO-Link resolution pressure [bar] |
0.1 |
| IO-Link resolution pressure [MPa] |
0.01 |
| IO-Link process data (cyclical) |
| function |
bit length |
| pressure |
14 |
| binary switching information |
2 |
|
| IO-Link functions (acyclical) |
application specific tag |
| Status_B High Resolution / CMPT = 3 |
| Profiles |
Smart Sensor ED2: Digital Measuring Sensor (0x000A), Identification and Diagnosis (0x4000) |
| Min. process cycle time [ms] |
3 |
| IO-Link resolution pressure [bar] |
0.05 |
| IO-Link resolution pressure [MPa] |
0.02 |
Sản phẩm cùng loại
Chat qua zalo
Để lại thông tin - Nhận giá ưu đãi