| Product characteristics |
| Output signal |
switching signal |
| Measuring range [bar] |
0…100 |
| Process connection |
threaded connection G 1/4 internal thread |
| Application |
| Special feature |
Gold-plated contacts |
| Application |
for industrial applications |
| Media |
liquids and gases |
| Conditionally suitable for |
use in gases at pressures > 25 bar only on request |
| Medium temperature [°C] |
-25…80 |
| Min. bursting pressure [bar] |
650 |
| Pressure rating [bar] |
300 |
| Type of pressure |
relative pressure |
| Electrical data |
| Operating voltage [V] |
18…30 DC |
| Current consumption [mA] |
< 90 |
| Min. insulation resistance [MΩ] |
100; (500 V DC) |
| Protection class |
III |
| Reverse polarity protection |
yes |
| Power-on delay time [s] |
0.2 |
| Integrated watchdog |
yes |
| Inputs / outputs |
| Number of inputs and outputs |
Number of digital outputs: 2 |
| Inputs |
| Analogue input (current) [mA] |
0…20 |
| Max. load [Ω] |
300 |
| Analogue input (voltage) [V] |
0…10 |
| Min. load resistance [Ω] |
90000 |
| Outputs |
| Total number of outputs |
2 |
| Output signal |
switching signal |
| Electrical design |
PNP/NPN |
| Number of digital outputs |
2 |
| Output function |
normally open / normally closed; (parameterisable) |
| Max. voltage drop switching output DC [V] |
2 |
| Permanent current rating of switching output DC [mA] |
250 |
| Switching frequency DC [Hz] |
< 170 |
| Short-circuit protection |
yes |
| Type of short-circuit protection |
pulsed |
| Overload protection |
yes |
| Measuring/setting range |
| Measuring range [bar] |
0…100 |
| Set point SP [bar] |
-24.6…100 |
| Note on setpoint SP |
|
| Reset point rP [bar] |
-25…99.6 |
| Note on setpoint SP |
|
| In steps of [bar] |
0.2 |
| Accuracy / deviations |
| Characteristics deviation [% of the final value] |
< ± 0,6 |
| Temperature drift per 10 K |
< ± 0.3 |
| Characteristics deviation analogue input |
< ± 0.3 |
| Temperature drift analogue input per 10 K |
< ± 0.1 |
| Temperature drift analogue input [°C] |
0…80 |
| Response times |
| Response time [ms] |
< 3 |
| Delay time programmable dS, dr [s] |
0, 0,1…50 |
| Damping for the switching output dAP [s] |
0…4 |
| Software / programming |
| Adjustment of the switch point |
programming button |
| Parameter setting options |
hysteresis / window; normally open / normally closed; switching logic; current/voltage input; Damping; adaptation of displayed values; display can be rotated and switched off; Display unit |
| Operating conditions |
| Ambient temperature [°C] |
-25…80 |
| Storage temperature [°C] |
-40…100 |
| Protection |
IP 67 |
| Mechanical data |
| Weight [g] |
291.5 |
| Materials |
stainless steel (1.4305 / 303); PBT; PC; PA; FKM |
| Materials (wetted parts) |
stainless steel (1.4305 / 303); ceramics; FKM |
| Min. pressure cycles |
100 million |
| Process connection |
threaded connection G 1/4 internal thread |
| Restrictor element integrated |
no (can be retrofitted) |
| Displays / operating elements |
| Display |
| Display unit |
3 x LED, green |
| display mode |
3 x LED, green |
| switching status |
2 x LED, yellow |
| function display |
alphanumeric display, 4-digit |
| measured values |
alphanumeric display, 4-digit |
|
| Display unit |
bar; psi; MPa |
| Remarks |
| Pack quantity |
1 pcs. |
| Electrical connection |
| Connection |
Connector: 1 x M12; Contacts: gold-plated |