| Product characteristics |
|
|
| Frequency range [Hz] |
2…10000 |
|
| Measuring principle |
capacitive |
|
| v-RMS |
|
|
| Measuring range of vibration [mm/s] |
0…45 |
|
| a-Peak / a-RMS |
|
|
| Measuring range of vibration |
0…50 g |
0…490.3 m/s² |
| Application |
|
|
| Application |
small machines, performance < 300 kW, speed 120…600 rpm |
|
| Electrical data |
|
|
| Operating voltage [V] |
18…30 DC |
|
| Current consumption [mA] |
< 50 |
|
| Min. insulation resistance [MΩ] |
100; (500 V DC) |
|
| Protection class |
III |
|
| Reverse polarity protection |
yes |
|
| Sensor type |
microelectromechanical system (MEMS) |
|
| Inputs / outputs |
|
|
| Number of inputs and outputs |
Number of digital outputs: 2 |
|
| Outputs |
|
|
| Output signal |
switching signal; IO-Link |
|
| Electrical design |
PNP/NPN; (configurable) |
|
| Number of digital outputs |
2 |
|
| Output function |
normally open / normally closed |
|
| Max. voltage drop switching output DC [V] |
2 |
|
| Max. current load per output [mA] |
100 |
|
| Short-circuit protection |
yes |
|
| Type of short-circuit protection |
pulsed |
|
| Overload protection |
yes |
|
| Measuring/setting range |
|
|
| Note on setpoint SP |
parameterisable |
|
| Frequency range [Hz] |
2…10000 |
|
| Measuring principle |
capacitive |
|
| Number of measurement axes |
1 |
|
| v-RMS |
|
|
| Measuring range of vibration [mm/s] |
0…45 |
|
| Set point SP [mm/s] |
0.2…45 |
|
| Reset point rP [mm/s] |
0…44.8 |
|
| In steps of [mm/s] |
0.2 |
|
| a-Peak / a-RMS |
|
|
| Measuring range of vibration |
0…50 g |
0…490.3 m/s² |
| Set point SP |
0.2…50 g |
2…490.3 m/s² |
| Reset point rP |
0…49.8 g |
0…488.3 m/s² |
| In steps of |
0.2 g |
2 m/s² |
| Crest |
|
|
| Measuring range of vibration |
1…50 |
|
| Set point SP |
2…50 |
|
| Reset point rP |
1…49 |
|
| In steps of |
1 |
|
| Temperature measurement |
|
|
| Measuring range [°C] |
-30…80 |
|
| Resolution [°C] |
0.1 |
|
| Set point SP [°C] |
-28…80 |
|
| Reset point rP [°C] |
-30…78 |
|
| In steps of [°C] |
2 |
|
| Accuracy / deviations |
|
|
| Accuracy |
≤ 4 kHz +/-10 %; ≥ 4…10 kHz: < 3 dB |
|
| Accuracy [K] |
± 2,5 K + (0,2 x (Umgebungstemperatur – Oberflächentemperatur)) |
|
| Linearity deviation |
2% |
|
| Software / programming |
|
|
| Parameter setting options |
Software |
|
| Diagnostic functions |
self-test |
|
| Interfaces |
|
|
| Communication interface |
IO-Link |
|
| Transmission type |
COM2 (38,4 kBaud); COM3 (230,4 kBaud) |
|
| IO-Link revision |
1.1 |
|
| SDCI standard |
IEC 61131-9: 2013-07 |
|
| Profiles |
Blob (0x0030); Measuring sensor (0x800A); Common Profile (0x4000) |
|
| SIO mode |
yes |
|
| Required master port type |
A |
|
| Process data analogue |
10 |
|
| Process data binary |
2 |
|
| Min. process cycle time [ms] |
3.6 |
|
| IO-Link functions (acyclical) |
filter for v-RMS, a-RMS, a-Peak; Hysteresis; window; switch points; switching logic |
|
| Supported DeviceIDs |
Type of operation |
DeviceID |
| |
Status A (COM2) |
1258 |
| |
Status B (COM2 / COM3) |
1370 |
| Note |
For further information please see the IODD PDF file under “Downloads” |
|
| Operating conditions |
|
|
| Ambient temperature [°C] |
-30…80 |
|
| Storage temperature [°C] |
-30…80 |
|
| Protection |
IP 67; IP 68; IP 69K |
|
| Mechanical data |
|
|
| Weight [g] |
116.2 |
|
| Type of mounting |
set screw |
|
| Materials |
housing: stainless steel (1.4404 / 316L) |
|
| Tightening torque [Nm] |
8 |
|
| Accessories |
|
|
| Items supplied |
set screw: 1 x 1/4″ 28 UNF / M8 |
|
| |
set screw: 1 x 1/4″28 UNF x 5/8″ DIN916 |
|
| Remarks |
|
|
| Pack quantity |
1 pcs. |
|
| Electrical connection |
Sản phẩm cùng loại
Chat qua zalo
Để lại thông tin - Nhận giá ưu đãi
Gọi cho CÔNG NGHIỆP VÀ TỰ ĐỘNG HÓA COZIC để nhận tư vấn tốt nhất
Địa chỉ - CÔNG NGHIỆP VÀ TỰ ĐỘNG HÓA COZIC
78 Hoà Minh 1 - Hoà Minh - Liên Chiểu - Đà Nẵng - Việt Nam
Văn phòng - CÔNG NGHIỆP VÀ TỰ ĐỘNG HÓA COZIC
VP: 16 Vũ Huy Tấn - Hoà Hiệp Nam - Liên Chiểu- Đà Nẵng- Việt Nam
Thông báo sẽ tự động tắt sau 5 giây ...
|