Cảm biến khí nén IFM SD2501

Product characteristics
Number of inputs and outputs Number of digital outputs: 2; Number of analogue outputs: 1
Measuring range
 
80…24720 scfh 1.5…412 scfm 1…275.6 ft/s
Process connection threaded connection 2″ NPT DN50
Application
Application for industrial applications
Media compressed air
Medium temperature [°C] -10…60
Min. bursting pressure [psi] 928
Pressure rating [psi] 232
Electrical data
Operating voltage [V] 18…30 DC; (according to EN 50178 SELV/PELV)
Current consumption [mA] < 80
Protection class III
Reverse polarity protection yes
Power-on delay time [s] 1
Inputs / outputs
Number of inputs and outputs Number of digital outputs: 2; Number of analogue outputs: 1
Inputs
Inputs counter reset
Outputs
Output signal switching signal; analogue signal; pulse signal; IO-Link; (configurable)
Electrical design PNP/NPN
Number of digital outputs 2
Output function normally open / normally closed; (parameterisable)
Max. voltage drop switching output DC [V] 2.5
Permanent current rating of switching output DC [mA] 150; (per output)
Number of analogue outputs 1
Analogue current output [mA] 4…20; (scalable)
Max. load [Ω] 500
Pulse output consumed quantity meter
Short-circuit protection yes
Type of short-circuit protection pulsed
Overload protection yes
Measuring/setting range
Measuring range
 
80…24720 scfh 1.5…412 scfm 1…275.6 ft/s
Display range
 
0…29660 scfh 0…494.5 scfm 0…330.8 ft/s
Resolution
 
20 scfh 0.5 scfm 0.2 ft/s
Set point SP
 
210…24710 scfh 3.5…411.8 scfm 2.4…275.5 ft/s
Reset point rP
 
90…24590 scfh 1.5…409.8 scfm 1…274.1 ft/s
Analogue start point ASP
 
0…19780 scfh 0…329.6 scfm 0…220.5 ft/s
Analogue end point AEP
 
4940…24720 scfh 82.4…412 scfm 55.1…275.6 ft/s
Low flow cut-off LFC
 
70…250 scfh 1.2…4.1 scfm 0.8…2.8 ft/s
In steps of
 
1 scfh 0.1 scfm 0.1 ft/s
Pressure monitoring
Measuring range [psi] -15…232
Display range [psi] -15…290
Resolution [psi] 1
Set point SP [psi] -13…232
Reset point rP [psi] -15…231
Analogue start point [psi] -15…186
Analogue end point [psi] 32…232
In steps of [psi] 1
Volumetric flow quantity monitoring
Measuring range
 
0…100000000 m³ 0…353146667.2 scf
Display range
 
0…100000000 m³ 0…353146667.2 scf
Set point SP
 
0.001…10000000 m³ 0.05…353146667.2 scf
Pulse value
 
0.001…10000000 m³ 0.05…353146667.2 scf
In steps of
 
0.0001 m³ 0.005 scf
Pulse length [s] 0.002…2
Temperature monitoring
Measuring range
 
-10…60 °C 14…140 °F
Display range
 
-24…74 °C -11.2…165.2 °F
Resolution
 
0.2 °C 0.5 °F
Set point SP
 
-9.7…60 °C 14.6…140 °F
Reset point rP
 
-10…59.7 °C 14…139.4 °F
Analogue start point
 
-10…46 °C 14…114.8 °F
Analogue end point
 
4…60 °C 39.2…140 °F
In steps of
 
0.1 °C 0.1 °F
Accuracy / deviations
Temperature coefficient [1/K] ± 0,07 % MW
Accuracy (in the measuring range) class 141: ± (2 % MW + 0,5 % MEW); class 344: ± (6 % MW + 0,6 % MEW) ; air quality to ISO 8573-1:2010; at medium temperature 73 °F
Repeatability ± (0,4 % MW + 0,1 % MEW)
Pressure monitoring