Cảm biến lưu lượng IFM SB2246 100 bar

Product characteristics
Process connection threaded connection G 1 internal thread
Temperature monitoring
Measuring range
 
-10…100 °C 14…212 °F
Application
Special feature Gold-plated contacts
Media Liquids; oil
Note on media
 
oil with viscosity: 46 mm²/s (40 °C)
Medium temperature [°C] -10…100
Pressure rating [bar] 100
Pressure rating [Mpa] 10
Note on pressure rating
 
at medium temperature >70°C: 80 bar / 8 MPa
Electrical data
Operating voltage [V] 18…30 DC; (according to EN 50178 SELV/PELV)
Current consumption [mA] < 50
Protection class III
Reverse polarity protection yes
Power-on delay time [s] < 3
Outputs
Total number of outputs 2
Output signal switching signal; analogue signal; frequency signal; IO-Link
Output function normally open / normally closed; (parameterisable)
Max. voltage drop switching output DC [V] 2
Max. current load per output [mA] 150; (200: …60 °C; Ambient temperature; 250: …40 °C; Ambient temperature)
Analogue current output [mA] 4…20
Max. load [Ω] 500
Short-circuit protection yes
Overload protection yes
Frequency of the output [Hz] 0…10000
Measuring/setting range
Measuring range
 
2…100 l/min 0.12…6 m³/h 32…1586 gph 0.55…26.4 gpm
Display range
 
0…120 l/min 0…7.2 m³/h 0…1902 gph 0…31.7 gpm
Resolution
 
0.1 l/min 0.01 m³/h 1 gph 0.01 gpm
Set point SP
 
0.7…100 l/min 0.04…6 m³/h 10…1586 gph 0.15…26.4 gpm
Reset point rP
 
0…99.3 l/min 0…5.96 m³/h 0…1574 gph 0…26.25 gpm
Frequency end point, FEP
 
6.7…100 l/min 0.4…6 m³/h 106…1586 gph 1.75…26.4 gpm
In steps of
 
0.1 l/min 0.01 m³/h 2 gph 0.05 gpm
Frequency at the end point FRP [Hz] 10…10000
In steps of [Hz] 10
Measuring dynamics 1:50
In steps of 10 Hz
Temperature monitoring
Measuring range
 
-10…100 °C 14…212 °F
Display range
 
-32…122 °C -25.6…251.6 °F
Resolution
 
0.1 °C 0.1 °F
Set point SP
 
-9.3…100 °C 15.2…212 °F
Reset point rP
 
-10…99.3 °C 14…210.8 °F
In steps of
 
0.1 °C 0.2 °F
Frequency start point, FSP
 
-10…78 °C 14…172.4 °F
Frequency end point, FEP
 
12…100 °C 53.6…212 °F
Frequency at the end point FRP [Hz] 10…10000
Accuracy / deviations
Flow monitoring
Accuracy (in the measuring range) ± 5 % MEW; (Q > 1 l/min; 20…70 °C Medium temperature)
Repeatability ± 1 % MEW
Temperature monitoring
Temperature drift 0,029 °C / K
Accuracy [K] 3 K (25°C; Q > 1 l/min)
Response times
Flow monitoring
Response time [s] 0.01
Damping for the switching output dAP [s] 0…5
In steps of [s] 0.1
Damping for the analogue output dAA [s] 0…5
In steps of [s] 0.1
Temperature monitoring
Dynamic response T05 / T09 [s] T09 = 120 (Q > 1 l/min)
Software / programming
Parameter setting options hysteresis / window; normally open / normally closed; switching logic; current/frequency output; damping for the switching output / analogue output; display can be rotated and switched off; standard unit of measurement; process value colour; calibration factor
Interfaces
Communication interface IO-Link
Transmission type COM2 (38,4 kBaud)
IO-Link revision 1.1
SDCI standard IEC 61131-9 CDV
Profiles Smart Sensor: Process Data Variable; Device Identification, Device Diagnosis
SIO mode yes
Required master port type A
Process data analogue 2
Process data binary 2
Min. process cycle time [ms] 3.2
Supported DeviceIDs
 
Type of operation DeviceID
Default 1046