Number of digital outputs: 2; Number of analogue outputs: 1
Process connection
threaded connection 3/4″ NPT
Temperature monitoring
Measuring range [°F]
14…212
Application
Special feature
Gold-plated contacts
Application
for industrial applications
Media
water; glycol solutions; coolants; oil
Note on media
oil 1 with viscosity: 10 mm²/s (40 °C)
oil 2 with viscosity: 46 mm²/s (40 °C)
Medium temperature [°F]
14…212
Pressure rating [bar]
40
Pressure rating [Mpa]
4
MAWP (for applications according to CRN) [bar]
40
Electrical data
Operating voltage [V]
18…30 DC; (according to EN 50178 SELV/PELV)
Current consumption [mA]
< 50
Protection class
III
Reverse polarity protection
yes
Power-on delay time [s]
< 3
Inputs / outputs
Number of inputs and outputs
Number of digital outputs: 2; Number of analogue outputs: 1
Outputs
Total number of outputs
2
Output signal
switching signal; analogue signal; frequency signal; IO-Link; (configurable)
Number of digital outputs
2
Output function
normally open / normally closed; (parameterisable)
Max. voltage drop switching output DC [V]
2
Permanent current rating of switching output DC [mA]
150; (per output 2 x 200 (…60 °C); 2 x 250 (…40 °C))
Switching cycles (mechanical)
10 million
Number of analogue outputs
1
Analogue current output [mA]
4…20
Max. load [Ω]
500
Short-circuit protection
yes
Overload protection
yes
Frequency of the output [Hz]
0…10000
Measuring/setting range
Measuring range
7…360 gph
0.1…6 gpm
Display range
0…432 gph
0…7.2 gpm
Resolution
1 gph
0.05 gpm
Set point SP
2…360 gph
0.05…6 gpm
Reset point rP
0…358 gph
0…5.95 gpm
Frequency end point, FEP
24…360 gph
0.4…6 gpm
In steps of
1 gph
0.05 gpm
Frequency at the end point FRP [Hz]
10…10000
Measuring dynamics
1:50
Temperature monitoring
Measuring range [°F]
14…212
Display range [°F]
-26…252
Resolution [°F]
2
Set point SP [°F]
16…212
Reset point rP [°F]
14…210
In steps of [°F]
2
Frequency start point, FSP [°F]
14…172
Frequency end point, FEP [°F]
54…212
Frequency at the end point FRP [Hz]
10…10000
Accuracy / deviations
Flow monitoring
Accuracy (in the measuring range)
± (4 % MW + 1 % MEW); (Q > 0,5 l/min; medium and operating temperature: +22 °C ± 4K)
Repeatability
± 1 % MEW
Temperature monitoring
Temperature drift
0,029 °C / K
Accuracy [K]
3 K (25°C; Q > 1 l/min)
Response times
Flow monitoring
Response time [s]
0.01
Damping for the switching output dAP [s]
0…5
Damping for the analogue output dAA [s]
0…5
Temperature monitoring
Dynamic response T05 / T09 [s]
T09 = 120 (Q > 1 l/min)
Software / programming
Parameter setting options
hysteresis / window; normally open / normally closed; switching logic; current output; medium selection; damping for the switching output / analogue output; display can be rotated and switched off; standard unit of measurement; process value colour
Interfaces
Communication interface
IO-Link
Transmission type
COM2 (38,4 kBaud)
IO-Link revision
1.1
SDCI standard
IEC 61131-9 CDV
Profiles
Smart Sensor: Process Data Variable; Device Identification