| Product characteristics |
| Number of inputs and outputs |
Number of digital outputs: 2; Number of analogue outputs: 1 |
| Measuring range |
| 10…1250 l/min |
0.3…103.6 m/s |
0.2…75 m³/h |
|
| Process connection |
threaded connection G 1/2 DN15 |
| Application |
| Application |
for industrial applications |
| Media |
compressed air |
| Medium temperature [°C] |
0…60 |
| Pressure rating [bar] |
16 |
| Pressure rating [Mpa] |
1.6 |
| Electrical data |
| Operating voltage [V] |
18…30 DC; (according to EN 50178 SELV/PELV) |
| Current consumption [mA] |
< 110 |
| Protection class |
III |
| Reverse polarity protection |
yes |
| Power-on delay time [s] |
1 |
| Inputs / outputs |
| Number of inputs and outputs |
Number of digital outputs: 2; Number of analogue outputs: 1 |
| Outputs |
| Total number of outputs |
2 |
| Output signal |
switching signal; analogue signal; pulse signal; IO-Link; (configurable) |
| Electrical design |
PNP |
| Number of digital outputs |
2 |
| Output function |
normally open / normally closed; (parameterisable) |
| Max. voltage drop switching output DC [V] |
2 |
| Permanent current rating of switching output DC [mA] |
250; (per output) |
| Number of analogue outputs |
1 |
| Analogue current output [mA] |
4…20; (scalable) |
| Max. load [Ω] |
500 |
| Pulse output |
consumed quantity meter |
| Short-circuit protection |
yes |
| Type of short-circuit protection |
pulsed |
| Overload protection |
yes |
| Measuring/setting range |
| Measuring range |
| 10…1250 l/min |
0.3…103.6 m/s |
0.2…75 m³/h |
|
| Display range |
| 0…1500 l/min |
0…124.3 m/s |
0…90 m³/h |
|
| Set point SP |
| 10…1250 l/min |
0.8…103.6 m/s |
0.6…75 m³/h |
|
| Reset point rP |
| 4…1244 l/min |
0.3…103.1 m/s |
0.2…74.6 m³/h |
|
| Analogue start point ASP |
| 0…938 l/min |
0…77.7 m/s |
0…56.3 m³/h |
|
| Analogue end point AEP |
| 312…1250 l/min |
25.9…103.6 m/s |
18.7…75 m³/h |
|
| In steps of |
|
| Volumetric flow quantity monitoring |
| Pulse value |
0.001…1000000 m³ |
| In steps of |
0.001 m³ |
| Pulse length [s] |
0,02…2 |
| Temperature monitoring |
| Measuring range [°C] |
0…60 |
| Display range [°C] |
-12…72 |
| Accuracy / deviations |
| Flow monitoring |
| Repeatability [% of the measured value] |
± 1,5 |
| Accuracy (in the measuring range) |
± (15 % MW + 1,5 % MEW); (maximum value to be achieved for air quality class 344 (DIN 8573-1); when using pipes of tolerance class T3/T4; inlet and outlet pipe lengths without edges and abrupt diameter changes; inner surface of the pipe free of burrs) |
| Temperature monitoring |
| Accuracy [K] |
± 2; (medium flow in the limit area of the flow measurement range) |
| Response times |
| Flow monitoring |
| Response time [s] |
0.1; (dAP = 0) |
| Damping for the switching output dAP in steps [s] |
0 – 0,2 – 0,4 – 0,6 – 0,8 – 1 |
| Software / programming |
| Parameter setting options |
Flow monitoring; quantity meter; Preset counter; Temperature monitoring; hysteresis / window; normally open / normally closed; current/pulse output; display can be rotated and switched off; Display unit; totaliser |
| Interfaces |
| Communication interface |
IO-Link |
| Transmission type |
COM2 (38,4 kBaud) |
| IO-Link revision |
1.1 |
| SDCI standard |
IEC 61131-9 CDV |
| Profiles |
no profile |
| SIO mode |
yes |
| Required master port type |
A |
| Process data analogue |
3 |
| Process data binary |
2 |
| Min. process cycle time [ms] |
4.1 |
| Supported DeviceIDs |
| Type of operation |
DeviceID |
| Default |
262 |
|
| Operating conditions |
| Ambient temperature [°C] |
0…60 |
| Storage temperature [°C] |
-20…85 |
| Max. relative air humidity [%] |
90 |
| Protection |
IP 65 |
| Mechanical data |
| Weight [g] |
579 |
| Materials |
PBT-GF20; NBR; PC; stainless steel (1.4301 / 304); PTFE; brass coated; FKM; aluminium powder-coated |
| Materials (wetted parts) |
stainless steel (1.4301 / 304); FKM; ceramics glass passivated; PEEK GF30; polyester; aluminium |
| Tightening torque [Nm] |
50 |
| Process connection |
threaded connection G 1/2 DN15 |
| Displays / operating elements |
| Display |
| Display unit |
5 x LED, green (Nl/min, Nm³/h, Nm/s, Nm³, °C) |
| function display |
1 x LED, green |
| switching status |
2 x LED, yellow |
| measured values |
alphanumeric display, 4-digit |
| programming |
alphanumeric display, 4-digit |
|
| Remarks |
| Remarks |
| MW = measured value |
| MEW = Final value of the measuring range |
| Measuring, display and setting ranges refer to the standard volume flow according to DIN ISO 2533. |
| For information about installation and operation please see the operating instructions. |
|
| Pack quantity |
1 pcs. |
| Electrical connection |
| Connection |
Connector: 1 x M12 |