Model |
FD-R200 |
Supported pipe diameter |
6″ (150 A), ø152 to ø191 5.98″ to 7.52″8″ (200 A), ø191 to ø220 7.52″ to 8.66″ |
Supported pipe materials |
Metal / resin*1 |
Supported fluids |
Various liquids (i.e. water, oils, chemicals)*1 |
Supported fluid temperature |
– 20 to + 120°C – 4.0 to + 248 °F (no freezing on the pipe surface)*2 |
Maximum rated flow |
Rated flow velocity range: 5.0 m/sFlow rate range (Typical):6″ (150 A): 5500 L/min 1400 gal/min 330 m3 /h8″(200 A): 9500 L/min 2500 gal/min 570 m3 /h |
Zero cut flow rate |
Zero cut: 0.3 m/s (default)*3Flow rate (Typical): 570 L / min 150 gal / min 36 m3 / h |
Display method |
Dual row, 5-digit display with white, 14-segment LED; Large status indicator; Output indicators; Stability indicator; Unit indicator |
Display update cycle |
Approx. 3 Hz |
Display resolution |
1 (L / min) |
Response time |
0.5 s / 1.0 s / 2.5 s / 5.0 s / 10.0 s / 30.0 s / 60.0 s / 120.0 s / 200.0 s (variable) |
Measurement accuracy |
Between 20 and 100% of F.S. : ±2.0% of RD*4*5Between 6 and 20% of F.S. : ±0.4% of F.S. *4*5 |
Protection circuit |
Power supply reverse connection protection, Power supply surge protection, Short-circuit protection for each output, Surge protection for each output |
Zero point error |
±0.5% of F.S.*4*6 |
Hysteresis |
Variable |
Flow units |
L / min, m3 / h, gal / min |
Integrated flow unit display |
1 / 10 / 100 / 1000 / 10000 (L) |
Pipe temperature measurement accuracy |
±3°C ±5.4°F (liquid temperature of – 20 to + 50°C, – 4 to + 122°F)±5°C ±9°F (liquid temperature of 50 to + 120°C, 122 to 248°F)(ambient operating temperature of 25°C 77°F)*4 |
Wiring specifications |
Power supply |
DC power supply: M12 4-pin connector / AC power supply: M4 screw terminal block (selectable) |
I/O |
When using a DC power supply: M12 4-pin connector / when using an AC power supply: M3 screw terminal block |
Input/Output (Selectable) |
Output (ch.1/ch.2) |
Control output / Integrated pulse output / Error output / Temperature alarm, NPN / PNP setting switchable,open collector output 30 VDC or less, max. 100 mA / ch., residual voltage: 2.5 V or less*7 |
Analog output (ch.1/ch.2) |
Flow rate analog output / Temperature analog output and 4 – 20 mA / 0 – 20 mA (selectable), load resistance: 500 Ω or less*7 |
External input (ch.2) |
Integrated flow reset input / Flow rate zero input / Origin adjustment input (selectable), short-circuit current: 1.5 mA or less, input time: 20 ms or more*7 |
Rating |
Power voltage |
20 to 30 VDC including 10% ripple (P-P), Class 2 / 100 to 240 VAC – 15% or + 10% (50 / 60 Hz) |
Current consumption |
When using a DC power supply: 200 mA or less (load current excluded), 400 mA or less (load current included) When using an AC power supply: 15 VA or less |
Environmental resistance |
Enclosure rating |
IP65 / 67 (IEC60259), IP69K (ISO20653), Enclosure Type 4X (NEMA250) |
Ambient temperature |
– 20 to + 60°C – 4.0 to 140 °F (no freezing)*2 |
Relative humidity |
5 to 90%RH (no condensation) |
Vibration resistance |
10 to 55 Hz, compound amplitude 1.5 mm 0.06″, XYZ axes 2 hours for each axis |
Shock resistance |
100 m/s2 , 16 ms pulse, XYZ axes, 1000 times for each axis |
Dimensions |
Main unit size: 218.5 mm × 66.9 mm × 70.7 mm 8.60″ × 2.63″ × 2.78″ |
Material |
Main unit |
Body: aluminum die-casting + coating / PPS, display: reinforced glass, connectors: SUS304-equivalent |
Unit rear |
Rubber |
Upper/lower bracket |
SUS304 |