| Product characteristics |
| Number of inputs and outputs |
Number of digital outputs: 1; Number of analogue outputs: 1 |
| Probe length L [mm] |
150…2000 |
| Process connection |
3/4″ NPT |
| Application |
| Special feature |
Gold-plated contacts |
| Media |
Liquids |
| Dielectric constant of the medium |
> 5 |
| Recommended media |
water; hydrous media |
| Medium temperature [°C] |
-20…100 |
| Tank pressure [bar] |
-1…16 |
| MAWP (for applications according to CRN) [bar] |
16 |
| Electrical data |
| Operating voltage [V] |
18…30 DC |
| Current consumption [mA] |
< 50 |
| Protection class |
III |
| Reverse polarity protection |
yes |
| Power-on delay time [s] |
< 3 |
| Inputs / outputs |
| Number of inputs and outputs |
Number of digital outputs: 1; Number of analogue outputs: 1 |
| Outputs |
| Total number of outputs |
2 |
| Output signal |
switching signal; analogue signal; IO-Link |
| Electrical design |
PNP/NPN |
| Number of digital outputs |
1 |
| Output function |
normally open / normally closed; (parameterisable) |
| Max. voltage drop switching output DC [V] |
2.5 |
| Permanent current rating of switching output DC [mA] |
150; (200 (…60 °C)) |
| Number of analogue outputs |
1 |
| Analogue current output [mA] |
4…20, invertible; (scalable) |
| Max. load [Ω] |
500 |
| Short-circuit protection |
yes |
| Type of short-circuit protection |
pulsed |
| Overload protection |
yes |
| Measuring/setting range |
| Probe length L [mm] |
150…2000 |
| Active range A [mm] |
L-40 |
| Inactive range I1 / I2 [mm] |
30 / 10 |
| Sampling rate [Hz] |
4 |
| Setting range |
| Set point SP [mm] |
≥ 15 …L-30 |
| Reset point rP [mm] |
≥ 10 …L-35 |
| In steps of [mm] |
1 |
| Hysteresis [mm] |
> 5 |
| Accuracy / deviations |
| Measuring error [mm] |
± 7 |
| Offset error [mm] |
5 |
| Resolution [mm] |
1 |
| Zero signal (current) [mA] |
4.0 |
| Full signal (current) [mA] |
20 |
| Temperature drift per 10 K |
± 0.2 % |
| Interfaces |
| Communication interface |
IO-Link |
| Transmission type |
COM2 (38,4 kBaud) |
| IO-Link revision |
1.1 |
| SDCI standard |
IEC 61131-9 |
| Profiles |
Smart Sensor: Process Data Variable; Device Identification, Device Diagnosis |
| SIO mode |
yes |
| Required master port type |
A |
| Process data analogue |
1 |
| Process data binary |
2 |
| Min. process cycle time [ms] |
2.3 |
| Supported DeviceIDs |
| Type of operation |
DeviceID |
| Default |
730 |
|
| Operating conditions |
| Ambient temperature [°C] |
-40…80 |
| Storage temperature [°C] |
-40…100 |
| Protection |
IP 68; IP 69K |
| Mechanical data |
| Weight [g] |
448 |
| Materials |
stainless steel (1.4404 / 316L); PEI; PFA; PBT; FKM |
| Materials (wetted parts) |
stainless steel (1.4404 / 316L); stainless steel (1.4435 / 316L); PTFE; FKM |
| Process connection |
3/4″ NPT |
| Displays / operating elements |
| Display |
| Display unit |
3 x LED, green |
| switching status |
2 x LED, yellow |
| level |
alphanumeric display, 4-digit |
| parameter setting |
alphanumeric display, 4-digit |
|
| Remarks |
| Pack quantity |
1 pcs. |
| Electrical connection – plug |
| Connection |